Energy Comparison - Pub Chain

The comparative test information in the following tables has been gathered from like-for-like metered energy trials conducted in a working kitchen of a large pub chain in the UK. The operator has determined the number of Adande Drawers to give equivalent capacity to existing units.

CHILLER - Application 1

Existing Unit

Adande Unit

Current Published Energy Consumption* - kWhr / 24hr
2.7
3.22
Actual Energy Consumption kWhr / 24hr
6.2
2.1
Actual Running Cost / Year based on 10p per kWhr
£228
£78
ANNUAL SAVING WITH ADANDE
66%
£150

CHILLER - Application 2

Existing Unit

Adande Unit

Current Published Energy Consumption* - kWhr / 24hr
2.7
3.22
Actual Energy Consumption kWhr / 24hr
5.7
2.0
Actual Running Cost / Year based on 10p per kWhr
£209
£72
ANNUAL SAVING WITH ADANDE
66%
£137

FREEZER - Application

Existing Unit

Adande Unit

Current Published Energy Consumption* - kWhr / 24hr
6.5
7.72
Actual Energy Consumption kWhr / 24hr
10.5
5.0
Actual Running Cost / Year based on 10p per kWhr
£384
£182
ANNUAL SAVING WITH ADANDE
52%
£201

Cabinet Air Temperatures - Average during Trials

Existing Unit

Adande Unit

Chiller - Application 1
Above set point
3.4°C
Chiller - Application 2
Above set point
3.1°C
Freezer - Application
Above set point
-18.4°C
Storage Capacity Based on 100 mm deep 1/1 GN
 
 
Chiller - Application 1
6
8
Chiller - Application 2
6
8
Freezer - Application
6
8